  Drives Service & Support > 2300 > 2364E > Specifications

Click for Dimensions

Approximate Shipping Weights
Output Current  (A DC) Current Code Unit Width and Depth Complete Unit Weight
180, 350 A, B 25"W x 20"D 675 lb (306kg)
900 C 30"W x 20"D 1000 lb (454 kg)
1500, 2000 D, E 55"W x 20"D 1950 lb (885 kg)
2500, 3000 F, G 65"W x 20"D 3000 lb (1361 kg)

 Electrical Specifications
Control Transformer kVA Ratings
1Nominal Input Voltage (V AC) 2Continuous Input Current
(A AC)
Nominal DC Bus Voltage
(V DC)
3Maximum Continuous DC Bus Current
(A DC)
NRU Current Code 4Rated DC Bus kW Basic Capacity Optional Standard Capacity for Control Bus Optional Extra Capacity for Control Bus
230 151 310 180 A 56 1 2 5
230 290 310 350 B 109 1 2 5
230 739 310 900 C 279 1 2 5
230 1229 310 1500 D 465 1 5 10
230 1637 310 2000 E 620 1 5 10
230 2050 310 2500 F 775 2 5 10
230 2458 310 3000 G 930 2 5 10
380 150 510 180 A 92 1 2 5
380 288 510 350 B 179 1 2 5
380 737 510 900 C 459 1 2 5
380 1227 510 1500 D 765 1 5 10
380 1636 510 2000 E 1020 1 5 10
380 2047 510 2500 F 1275 2 5 10
380 2455 510 3000 G 1530 2 5 10
460 149 620 180 A 112 1 2 5
460 288 620 350 B 217 1 2 5
460 737 620 900 C 558 1 2 5
460 1227 620 1500 D 930 1 5 10
460 1635 620 2000 E 1240 1 5 10
460 2046 620 2500 F 1550 2 5 10
460 2454 620 3000 G 1860 2 5 10
575 149 775 180 A 140 1 2 5
575 288 775 350 B 271 1 2 5
575 737 775 900 C 698 1 2 5
575 1226 775 1500 D 1163 1 5 10
575 1635 775 2000 E 1550 1 5 10
575 2045 775 2500 F 1938 2 5 10
575 2453 775 3000 G 325 2 5 10
1Refer to Functional Specifications table for AC input specifications.
2AC line current shown is for NRU with basic capacity control transformer. Refer to Table E for AC input current if you have selected a control power source upgrade option.
3 Refer to Functional Specifications table for NRU overload capability.
4Rated DC bus kW is the power available on the DC thru bus. This value is independent of control transformer selection. To calculate the input kVA, use this formula:


Functional Specifications

AC Input Frequency Tolerance 45 to 65 Hz
AC Input Voltage Tolerance ± 10%
Overload Capability 150% maximum DC bus current for 60 seconds, 200% for 10 seconds following continuous operation
Overload Duty Cycle    1 minute out of 20 minutes at rated load and temperature
Minimum Continuous Load Requirement † 33% of rated DC bus continuous current
† If the total continuous DC input current of the load is less than 33% of the rate NRU DC bus continuous current, the bus current may become discontinuous.


Input Currents of NRU with Control Source Upgrade Options
Nominal Input Voltage (V AC) NRU Current Code Continuous Input Current of NRU with Standard Capacity Control Source Upgrade Option 6P
(A AC)
Continuous Input Current of NRU with Extra Capacity Control Source Upgrade Option 6PX (A AC)
230 A 156 169
230 B 294 308
230 C 744 757
230 D 1246 1268
230 E 1655 1676
230 F 2063 2086
230 G 2471 2493
380 A 152 160
380 B 291 299
380 C 740 748
380 D 1238 1251
380 E 1646 1659
380 F 2054 2068
380 G 2463 2476
460 A 151 158
460 B 290 297
460 C 739 746
460 D 1236 1246
460 E 1644 1655
460 F 2052 2063
460 G 2460 2471
575 A 150 156
575 B 289 294
575 C 738 744
575 D 1233 1242
575 E 1642 1650
575 F 2050 2059
575 G 2458 2467


Thru Bus Ratings per Unit
Unit DC Bus Current (A DC) Thru Bus Rating(A DC)
180 800
350 800
900 1600
1500 1600
2000 3000
2500 3000
3000 3000
Operating Conditions
Altitude1 1000 meters (3,300 ft)
Ambient Temperature2 0º to 40º C (32º to 104º F)
Relative Humidity 5% to 95%, non-condensing
1For altitudes higher than 1000 meters, derate using Figure 1.
2For temperatures greater than 40º C, derate using Figure 2.





Operating Sound Level
 DC Bus Current (A DC)  Current Code  Average Operating Sound Level (dB) 1
180, 350 A, B 78
900 C 77
1500, 2000 D, E 73
2500, 3000 F, G 76
1Sound level determined using "A"-type weighting.