Functional Specifications
AC Input Frequency Tolerance 45 to 65 Hz
AC Input Voltage Tolerance ± 10%
Motoring Output Current Overload 150% of rated cur rent for 60 seconds
Regeneration Output Current Overload 150% of rated current for 60 seconds
150% of rated current for 30 seconds
(380 or 460V AC N-code RGUs at 40°C)
150% of rated current for 30 seconds
( 575V AC N-code RGUs at 30°C)
Output Voltage Variation 10% maximum for a ±100% DC output current step load change
Resolution of Output Voltage Selection 1. 0V
Voltage Regulator Bandwidth 200 radians/sec nominal
Current Regulator Bandwidth 1200 radians/sec nominal
† If the total continuous DC input current of the load is less than 33% of the rate DC bus continuous current, the bus current may become discontinuous.

Operating Sound Level
RGU Current Code Average Operating Sound Level (dB) †
J 75
K 77
L 84
M 82
N 85
† Sound level determined using "A"-type weighting.

Electrical Specifications I
1Continuous AC Line Current Control Transformer kVA Ratings
RGU Current Code Nominal Input Voltage (V AC) Basic Capacity
(A AC)
Standard Capacity
(A AC)
Input Power (kVA) Nominal DC Bus Voltage (V DC) Maximum Continuous DC Bus Current
(A DC)
2Rated DC Bus (kW) Basic Capacity
(kVA)
Standard Capacity
(kVA)
J 380 77 77 51 564 85 49 2.0 5.0
K 380 182 182 120 564 200 116 2.0 5.0
L 380 330 330 217 564 363 211 2.0 5.0
M 380 678 678 447 564 746 433 5.0 5.0
N 380 906 906 596 564 997 578 5.0 10.0
J 460 77 77 61 683 85 59 2.0 5.0
K 460 182 182 145 683 201 141 2.0 5.0
L 460 330 330 263 683 364 255 2.0 5.0
M 460 678 678 541 683 749 524 5.0 5.0
N 460 906 906 722 683 1000 700 5.0 10.0
J 575 77 77 62 848 88 74 2.0 5.0
K 575 182 182 181 848 201 170 2.0 5.0
L 575 286 286 285 848 326 276 2.0 5.0
M 575 602 602 600 848 686 582 5.0 5.0
N 575 802 802 799 848 914 775 5.0 10.0
1The continuous AC line current values apply to both motoring and regenerating operations.
2Rated DC bus kW is the power available on the DC thru bus at rated voltage and current.

Electrical Specifications II

RGU Current Code Input Voltage (V AC) Internal Capacitance
(uF)
Line Inductance
(uH))
Overcurrent Trip
(Arms)
Overcurrent Trip Reference (TP20 Volts) Overvoltage Trip
(V DC)
Overvoltage Trip Reference
(TP22 Volts)
Burden Resistor (Ohms) Warning Temperature
(ºC)
Trip Temperature
(ºC)
 J 380 6450 1193 173 4.55 820 3.75 8.87 80 100
K 380 12000 510 409 4.55 820 3.75 7.50 80 100
L 380 15000 317 743 4.55 820 3.75 6.19 80 100
M 380 24000 137 1526 4.55 820 3.75 4.02 80 110
N 380 24000 102 2039 4.55 820 3.75 3.01 80 110
J 460 6450 1193 173 4.55 820 3.75 8.87 80 100
K 460 12000 510 409 4.55 820 3.75 7.50 80 100
L 460 15000 317 743 4.55 820 3.75 6.19 80 100
M 460 24000 137 1526 4.55 820 3.75 4.02 80 110
N 460 24000 102 2039 4.55 820 3.75 3.01 80 110
J 575 2860 1853 140 4.55 1025 4.69 11.0 80 100
K 575 6000 832 409 4.55 1025 4.69 7.50 80 100
L 575 15000 404 644 4.55 1025 4.69 7.15 80 100
M 575 24000 191 1354 4.55 1025 4.69 4.53 80 110
N 575 24000 144 1805 4.55 1025 4.69 3.40 80 110

Operating Conditions
Altitude 3,300 feet (1,000 meters)1
Ambient Temperature 0º to 40º C (32º to 104º F)2
Relative Humidity 5% to 95%, non-condensing
1For altitudes higher than 1000 meters, derate RGU using Figure 2.
2For temperatures greater than 40º C, derate RGU using Figure 3.

Storage Conditions
Ambient Temperature 0º to 40º C (32º to 104º F)
Relative Humidity 5% to 95%, non-condensing