Drives Service & Support
Product Advisories: DriveLogix5730
Date: September 2005 Ref: CPAG 2005-09-002
The purpose of this Product Service Advisory is to inform you of a functional issue that exists with the following Rockwell Automation products:
20D XXXXXXXXXXXXXK
20D XXXXXXXXXXXXXL |
DriveLogix5730 DriveLogix5730 |
Shipped between Feb 1, 2004 and Aug 10 th, 2005 Noted on Data Name Plate |
20N XXXXXXXXXXXXXK
20N XXXXXXXXXXXXXL |
LiquiFlo with DriveLogix5730 |
Shipped between Feb 1, 2004 and Aug 10 th, 2005 Noted on Data Name Plate |
| 20D-DL2-CKE0 |
DriveLogix Expanded Cassette |
Shipped between Feb 1, 2004 and Aug 10 th, 2005 |
Problem Description
The DriveLogix5730 has reduced battery life. - Functional Issue - An anomaly in a component will drain the battery on the DriveLogix5730 controller and greatly reduce the life of the battery.
Product Identification
Product affected by this Mandatory Product Service Advisory includes all Drive Logix5730 controllers produced before August 10, 2005.
Affected ship dates are as follows:
Product |
Start Shipment Date |
End Shipment Date |
20D XXXXXXXXXXXXXK |
Feb / 2004 |
Aug 10 th, 2005 |
20D XXXXXXXXXXXXXL |
Feb / 2004 |
Aug 10 th, 2005 |
20N XXXXXXXXXXXXXK |
Sep / 2004 |
Aug 10 th, 2005 |
20N XXXXXXXXXXXXXL |
Sep / 2004 |
Aug 10 th, 2005 |
20D-DL2-CKE0 |
Sep / 2004 |
Aug 10 th, 2005 |
Problem Correction
- The DriveLogix5730 controller has been corrected as of Aug 10 th, 2005 to assure proper functionality.
- The DriveLogix5730 main control board must be upgraded with corrected components.
DriveLogix Drive 20DXXXXXXXXXXXXXK *, Series A
DriveLogix Drive 20DXXXXXXXXXXXXXL *, Series A
LiquiFlo Drive 20NXXXXXXXXXXXXXK *, Series A
LiquiFlo Drive 20NXXXXXXXXXXXXXL *, Series A
DriveLogix Spare Parts 20D-DL2-CKE0, Series -
Requested Customer Action
Each notified customer should take the following actions:
- Confirm that they have the affected products and identify quantity and part number.
- Immediately contact their local Rockwell Automation Sales and Support office to determine the appropriate course of action. Together, the local office and customer will determine the correction for their situation.
- Upon receiving the replacement cassette perform the following:
- Identify the installed options of the original cassette.
- Transfer these options to the replacement cassette.
- The following reference information is related to cassette options:
- 20D-IN001E-EN-P Installation Instructions – Stegmann Feedback Option for PF700S Drive.
- 20D-IN002B-EN-P Installation Instructions – Resolver Feedback Option for PF700S Drive.
- 20D-IN004A-EN-P Installation Instructions – Multi-Device Interface for PF700S Drive.
- 20D-IN009A-EN-P Installation Instructions – Second Encoder Option for PF700S Drive.
- 20D-IN010A-EN-P Installation Instructions – SynchLink for PF700S Drive.
- 20D-IN017A-EN-P Installation Instructions – Heidenhain Feedback Option for PF700S Drive.
- 20D-IN008B-EN-P Installation Instructions – Compact I/O Cable for DriveLogix5730 controller.
- 20D-IN012A-EN-P Installation Instructions – Embedded EtherNet/IP Option Card for DriveLogix5730 controller.
- 20D-IN013A-EN-P Installation Instructions – Logix Expansion Board for DriveLogix5730.
- 20D-UM003A-EN-P User Manual – DriveLogix5730 Controller for PF700S Drives with Phase II Control.
These Instructions and User Manual can be found on the Rockwell Automation Literature Library:
Link to Literature Library: www.rockwellautomation.com/literature
|