Drives Service & Support
Product Advisories: SLC 500 DeviceNet Scanner Module Catalog Number 1747-SDN Series C, FRN 8.003 and earlier
Ref: ACIG 2007-09-002
The purpose of this Product Safety Alert is to inform you of a functional issue that exists with:
- 1747-SDN DeviceNet Scanner Module, Series C with FRN 8.003 and earlier firmware
Issue Description
With the 1747-SDN module, series C with FRN 8.003 and earlier firmware hereafter referred to
as SDN module, the following functional issue exists:
Firmware revision 8.003 and earlier has internal M0 file bits set to random values upon powerup.
On 1747-SDN module startup, if an explicit message or passthrough message is sent before
outputs are transferred from the SLC controller to the M0 file with a COPY command, the
random values will be used as outputs. If the 1747-SDN module is in run mode, this could cause
outputs to turn On unexpectedly when the scanner transmits data to connected output devices.
Firmware revision 8.004 corrects this anomaly.
Product Identification
The 1747-SDN modules affected by this Mandatory Product Safety Alert can be identified with
the following catalog numbers, series and firmware revision.
- 1747-SDN, Series C, FRN 8.003 and earlier
The series and FRN number are located on the product label on the left side of the SDN module.
Rockwell Automation shipped the affected products beginning April 1, 2007 through August 17,
2007.
Unopened Shipping Cartons- 1747-SDN modules affected by this Mandatory Product Safety
Alert still in unopened shipping cartons can be identified by the cat. nos., series, and firmware
revision which are located on the shipping carton label.
Issue Correction
This firmware anomaly has been corrected with FRN 8.004 firmware. All corrected 1747-SDN
modules will be marked with the FRN 8.004 firmware number. Shipping carton labels will also
be marked with FRN 8.004. All other product identification will remain the same.
All 1747-SDN modules, series C with FRN 8.003 and earlier firmware, should be upgraded to
FRN 8.004 to avoid possible 1747-SDN module anomalies. Firmware updates can be done via
ControlFlash. Customers can obtain a ControlFlash upgrade for their SDN module by contacting
Technical Support at (440) 646-5800 or use the attached FaxBack form to order firmware
upgrades.
Requested Customer Action
Each notified customer should take the following actions:
- Confirm that they have the affected products.
- Immediately contact their local Rockwell Automation Sales and Support office to determine
the appropriate course of action. Together, the local office and customer will determine the
correction for their situation.
|