Service Conditions

AC Line Distribution Capacity (Maximum) Three-phase 575 VAC, with 30,000 amps symmetrical fault current capacity
Control Method All digital, pulse-width-modulated (PWM)
 Carrier Frequency 4 kHz, 6kHz, or 8 kHz, software selectable
 Displacement Power Factor 0.96
Line Frequency 50/60 Hz (±5 Hz)
Line Voltage Variation -10% to +10%
Line Dip RideThrough 500 milliseconds
Linearity 0.05 (Speed reference to output frequency)
Long-term Frequency Stability 0.01%
Minimum Frequency Range 0.5 - 30 Hz
Maximum Frequency Range 30 - 240 Hz
Maximum Load 150% for 1 minute (based on Drive nameplate rating)
Motor Lead Lengths 76 meters (250 feet) total (See table 3.7 for more information)
Overcurrent Trip IET 200% rated Drive current

Environmental Conditions
Operating Temperature 0° to +40°C (32° to 104°F) enclosed Drives
0° to +55°C (32° to 131°F) - open chassis (cover removed)
Storage Temperature -40° to 65°C (-40° to 149°F)
Humidity 5 to 95% (non-condensing)
Altitude Do not install the Drive above 1000 meters (3300 feet) without derating output power. For every 91.4 meters (300 feet) above 1000 meters (3300 feet) up to 3033 meters (10,000 feet), derate the output current by 1%. Above 3033 meters (10,000 feet), contact your local Allen-Bradley sales office for assistance.