Service Conditions |
| AC Line Distribution Capacity (Maximum) |
Three-phase 575 VAC, with 30,000 amps symmetrical fault current capacity |
| Control Method |
All digital, pulse-width-modulated (PWM) |
| Carrier Frequency |
4 kHz, 6kHz, or 8 kHz, software selectable |
| Displacement Power Factor |
0.96 |
| Line Frequency |
50/60 Hz (±5 Hz) |
| Line Voltage Variation |
-10% to +10% |
| Line Dip RideThrough |
500 milliseconds |
| Linearity |
0.05 (Speed reference to output frequency) |
| Long-term Frequency Stability |
0.01% |
| Minimum Frequency Range |
0.5 - 30 Hz |
| Maximum Frequency Range |
30 - 240 Hz |
| Maximum Load |
150% for 1 minute (based on Drive nameplate rating) |
| Motor Lead Lengths |
76 meters (250 feet) total (See table 3.7 for more information) |
| Overcurrent Trip IET |
200% rated Drive current |
| Environmental Conditions |
| Operating Temperature |
0° to +40°C (32° to 104°F) enclosed Drives
0° to +55°C (32° to 131°F) - open chassis (cover removed) |
| Storage Temperature |
-40° to 65°C (-40° to 149°F) |
| Humidity |
5 to 95% (non-condensing) |
| Altitude |
Do not install the Drive above 1000 meters (3300 feet) without derating output power. For every 91.4 meters (300 feet) above 1000 meters (3300 feet) up to 3033 meters (10,000 feet), derate the output current by 1%. Above 3033 meters (10,000 feet), contact your local Allen-Bradley sales office for assistance. |
|