Drives Service & Support
Click for Dimensions or Specifications
| Drive Inputs |
| Analog Speed Reference |
0 to 10 VDC or 0 to 20 mA |
| Start |
Edge-sensitive signal that must see an open-to-closed contact transition. This transition may be a momentary or fixed closure. |
| Stop |
An open contact that must be closed when the Drive is running. The Drive will remain off as long as the contact is open. |
| IET Reset |
Edge-sensitive signal that must see an open-to-closed contact transition. This transition may be a momentary or fixed closure. |
| Forward/Reverse |
An open contact to assert the forward direction and a closed contact to assert the reverse direction. |
| Function/Loss |
An open contact that must be closed when the Drive is running. When the contact is open, the Drive turns off. The Drive will remain off as long as the contact is open. |
| Drive Outputs |
Analog Output
(0 to 10 VDC scaled signal) |
The scaled signal is selected through parameter F-29 and can be one of the following:
- Output Voltage: 0 to 632 VAC
- % Load (Amps): 0 to 2000 % (Percentage of output amps based on the Drive nameplate.)
- RPM/Engineering Unit: Minimum to maximum RPM or minimum to maximum of any engineering unit (See parameter F-08)
- % Selected Speed Reference: 0 to 100% (Percentage of the selected reference signal range)
|
| Snubber Resistor Braking |
Snubber resistor control signal used by an optional snubber resistor |
| Output Status Relay |
115 VAC/24 VDC, 0.5 Amp, relay output (One Form A and one Form B contact wired with a single common.) |
|