Drive Inputs
Analog Speed Reference 0 to 10 VDC  or  0 to 20  mA
Start Edge-sensitive signal that must see an open-to-closed contact transition. This transition may be a momentary or fixed closure.
Stop An open contact that must be closed when the Drive is running. The Drive will remain off as long as the contact is open.
IET Reset Edge-sensitive signal that must see an open-to-closed contact transition. This transition may be a momentary or fixed closure.
Forward/Reverse  An open contact to assert the forward direction and a closed contact to assert the reverse direction.
Function/Loss  An open contact that must be closed when the Drive is running. When the contact is open, the Drive turns off. The Drive will remain off as long as the contact is open.
Drive Outputs
Analog Output
(0 to 10 VDC scaled signal)
The scaled signal is selected through parameter F-29 and can be one of the following:
  • Output Voltage: 0 to 632 VAC
  • % Load (Amps): 0 to 2000 % (Percentage of output amps based on the Drive nameplate.)
  • RPM/Engineering Unit: Minimum to maximum RPM or minimum to maximum of any engineering unit (See parameter F-08)
  • % Selected Speed Reference:  0 to 100% (Percentage of the selected reference signal range)
Snubber Resistor Braking Snubber resistor control signal used by an optional snubber resistor
Output Status Relay 115 VAC/24 VDC, 0.5 Amp, relay output (One Form A and one Form B contact wired with a single common.)