Drives Service & Support > 1329I > Drive Specifications

Input Ratings
AC line voltage:
  • 380 to 460 VAC, 3-phase
  • 200 to 230 VAC, 3-phase
  • 200 to 230 VAC, 1-phase
  • 115 VAC, 1-phase
AC line frequency: 48 to 62 Hz
AC line voltage variation: +/-10%
AC line current
 Input Voltage  Unit HP  Input Current
 460 VAC  1 HP  2.5 A rms continuous
 460 VAC  2 HP  4.2 A rms continuous
 460 VAC  3 HP  6.2 A rms continuous
 460 VAC  5 HP  9.9 A rms continuous
 230 VAC  1 HP  4.5 A rms continuous
 230 VAC  2 HP  7.6 A rms continuous
 230 VAC, 1-phase  1 HP  5.8 A rms continuous
 230 VAC, 1-phase  2 HP  14 A rms continuous
115 VAC 1 HP  14 A rms continuous
Max allowable AC line distribution KVA 100 KVA maximum for 115 VAC to 460 VAC input
Output Ratings
Horsepower ratings:
  • 1, 2, 3 and 5 HP at 460 VAC
  • 1, 2 HP at 230 VAC
  • 1 HP at 115 VAC
Output voltage:
  • 380 to 460 VAC, 3-phase
  • 200 to 230 VAC, 3-phase
  • 115 VAC, 3-phase
Maximum continuous output current
Input Voltage Unit HP Output Current  (Motor Rated Amps)
 460 VAC 1 HP 1.7 A
 460 VAC 2 HP 3.2A
 460 VAC 3 HP 4.5 A
460 VAC 5HP 6.9 A
230 VAC 1 HP 3.4 A
230 VAC 2 HP 6.4 A
230 VAC, 1-phase 1 HP 3.4 A
230 VAC, 1-phase 2HP 6.4 A
115 VAC 1 HP 6.8 A
Maximum output current:
 Input Voltage Unit HP Maximum Output Current
(150% Rated Amps)
460 VAC 1 HP 2.55 A
460 VAC 2 HP 4.8 A
460 VAC 3 HP 6.75 A
460 VAC 5 HP 10.35 A
230 VAC 1 HP 5.1 A
230 VAC 2 HP 9.6 A
230 VAC, 1-phase 1 HP 5.1 A
230 VAC, 1-phase 2 HP 9.6 A
115 VAC 1 HP 10.2 A
Important: Maximum current ratings above are for the CT rating. When selected, the maximum output current will be limited to 110%.
Output frequency 3 to 120 Hz
Carrier frequency 8 kHz
Operating Performance
Speed regulation 1% (1% of base speed, 180 to 1800 RPM, constant torque)
Speed range 20:1 (90 to 1800 RPM, constant torque)
Voltage regulation: 3% of maximum rated voltage
Power dip ride-through time: 500 msec minimum
Drive efficiency: >95% (at rated amps, 115-460 V, 60 Hz)
Operating Specifications
Operating temperature 0°C to 40°C (32°F to 104°F) ambient
Storage temperature -40°C to 65°C (-40°F to 149°F)
Altitude 1000 meters (3300 feet maximum) without derating. For every 91.4 (300 feet) above 1000 meters, derate the current by 1%. Above 3000 (10,000 feet), consult your Allen-Bradley Sales Office
Humidity 5% to 95%, non-condensing
Service factor 1.0
Mechanical Specifications
Motor enclosure type Totally enclosed, 24 VDC blower cooled (TEBC)
Required airflow Required clearance for blower intake = 1 in
Drive Protection/Fault Detection
Output overcurrent Trip level = 200% of max peak rated current
Output ground fault Trip level = 200% of max peak rated current
DC bus overvoltage
Line Voltage Trip Level
460 VAC 830 VDC
230 VAC 415 VDC
115 VAC 208 VDC
Motor thermal overload:
  • Trip time = 1 minute at 150% of rated current (CT)
  • Trip time = 1 minute at 110% of rated current (VT)
DC bus undervoltage
Line Voltage Trip Level
460 VAC 435 VDC
380 VAC 358 VDC
230 VAC 218 VDC
115 VAC 109 VDC
I/O Specifications  
Important: All signals are isolated from the incoming 3-phase power.
Analog inputs  
0 to 10 V
  • Input impedance: 50 kW
  • Resolution: 0.11%
4 to 20 mA
  • Input impedance: 250 W
  • Resolution: 0.14%
Analog output  
0 to 10 V
  • Minimum load resistance: 2 kW
  • Resolution: 0.4%
Logic inputs (Stop, Start, Reset, Fwd/Rev, RPM/%Load, Function Loss, Preset Speed)
24 VDC sourcing inputs
  • Maximum input voltage: 28.8 VDC
  • Input current @ 24 VDC: 10 ma
  • Maximum OFF state voltage: 5 VDC
  • Minimum ON state voltage: 15 VDC
Relay output (1 form A N.O. contact)
Maximum current (resistive or inductive) 1 A
Minimum current 10 ma
Maximum voltage 28 VDC, 250 VAC
Approvals and Standards Compliance
Approvals
Designed to meet these standards:
  • FCC Class A and B, ICE 146-1-1, VDE 0871 and VDE 0875
  • U L ®
  • UL508C U L ®
  • C CSA 22.2