Click for Dimensions or Input/Output Ratings
| Operating Environment | ||
| Temperature | -10°C to + 50°C (+14°F to +122°F) | |
| Relative Humidity | 5 to 95% non-condensing. | |
| Altitude | 3,300 feet (1,000 meters) maximum without 10% derating | |
| Vibration | Below 0.5G, 0.8 mm peak-to-peak amplitude, x-y-z direction. | |
| Shock | 16G peak for 11ms duration. | |
| Storage Environment | ||
| Temperature | -25°C to +65°C (-13°F to +149°F) | |
| Relative Humidity | 5 to 95% non-condensing | |
| Enclosure | ||
| Type | NEMA Type 1 (IP20). Indicated by catalog number. | |
| Input Power Specifications | ||
| Drive Rating | ZAA-GAA | AAB-CAB |
| Voltage: ±10% | 200-230V AC, ±10% | 380-460V AC, |
| Frequency | 50/60 Hz, ±5% | 50/60 Hz, ±5% |
| Phase | 1 or 3-phase | 3-phase |
| Bus Overvoltage Trip | 430V DC | 820V DC |
| Bus Undervoltage Trip | 160V DC | 310V DC |
| Bus Overcurrent Trip | 200% IET | |
| Power Ride-Thru | 15 ms or longer depending on the load. | |
| Control Ride-Thru | 100 ms or longer depending on the load. | |
| Control Logic Noise Immunit | Showering arc transients from 350 to 2,000 volts. | |
| Load Requirements | ||
| A balanced 3-phase inductive motor load is typical. Other motor loads may require application assistance. | ||
| Output Power Specifications | ||
| Waveform | Sine coded pulse width modulated waveform. | |
| Voltage | Drive Rating ZAA-GAA: 0 to applied input voltage, 200V AC, 208V AC, or 230V AC -- maximum output voltage cannot exceed applied input voltage. Drive Rating AAB-CAB: 0 to applied input voltage, 380V AC, 415V AC, or 460V AC -- maximum output voltage cannot exceed applied input voltage. |
|
| Frequency Range: | Programmable Min and Max Limits 0 to 400 Hz remote frequency command. 0.5 to 400 Hz local frequency command. |
|
| Frequency Regulation: | ±0.5% of selected maximum output frequency -10 to +50....C ambient temperature range. |
|
| Accel/Decel: | Four independently programmable accel times. Four independently programmable decel times. Each time may be programmed over a range from 0.1 to 1600 seconds. If 0 is entered, the drive will default to 40 ms. |
|
| Accel Stall Protection: | 140% of rated current. | |
| Decel Stall Protection: | 380V DC for 230V AC drive input voltage. 760V DC for 460V AC drive input voltage. |
|
| Volts-per-Hertz: | Selectable constant or square v/Hz curves. | |
| DC Boost: | 0-40% of maximum output voltage adjustable in 1% increments. | |
| Starting Torque: | 150% nominal at 5 Hz. | |
| Braking Torque: | DC Brake: 20% of rated torque (standard) programmable duration and voltage Heavy Duty Dynamic Brake: 100% of rated torque. |
|
| Stopping Frequency: | 0.5-60 Hz | |
| Intermittent Overload Capability: | Standard: 140% of rated output current for 1 minute. Inverse Trip: 125% of programmable overload trip level for one minute. |
|
| Drive Overload Trip: | Programmable overload trip function set to motor nameplate value. | |
| Ground Fault: | Current sensors detect output ground fault at drive output leads. | |
| Frequency Control Inputs | ||
| Digital Input Frequency Resolution: | Local Speed Control 0.01 Hz up to 100 Hz. 0.1 Hz over 100 Hz. |
|
| Analog Input Frequency Resolution: | Remote Speed Pot (Control Terminal Block, Terminals 1, 2 and 3) 0.1 Hz up to 100 Hz. 0.2 Hz up to 200 Hz. 0.5 Hz over 200 Hz. 0-5V DC Input (Control Terminal Block, Terminals 3 and 4) 0.1 Hz up to 100 Hz. 0.2 Hz up to 200 Hz. 0.5 Hz over 200 Hz. 0-10V DC Input (Control Terminal Block, Terminals 3 and 4) 0.1 Hz up to 100 Hz. 0.2 Hz up to 200 Hz. 0.5 Hz over 200 Hz. 4-20 mA Input (Control Terminal Block, Terminals 3 and 5) 0.1 Hz up to 100 Hz. 0.2 Hz up to 200 Hz. 0.5 Hz over 200 Hz. |
|