Allen-Bradley Home
Drives Service & Support

General Resources

  Drives Service & Support > Legacy > 1336 > Input/Output Ratings > C003-C200

0 to 575V AC (maximum output voltage cannot exceed applied input voltage).

Input Current and kVA

Output Current and kVA

Amps In Rating Code kVA In 500 Vac kVA In 575 Vac kVA In 600 Vac Input Power Factor Displacement Angle kW/kVA
3.2 B003 2.8 3.2 3.2 0.95 0.85
5.1 B005 4.4 5.1 5.1 0.95 0.85
7.7 B007 6.7 7.7 7.7 0.95 0.85
10.2 B010 8.9 10.2 10.2 0.95 0.85
15.0 B015 13.0 15.0 15.0 0.95 0.90
19.0 B020 17.0 19.0 19.0 0.95 0.90
24.0 B025 21.0 24.0 24.0 0.95 0.90
29.0 B030 25.0 29.0 29.0 0.95 0.90
39.0 B040 33.0 38.0 38.0 0.95 0.90
48.0 B050 42.0 48.0 48.0 0.95 0.90
73.0 B075 63.0 73.0 73.0 0.95 0.90
97.0 B100 84.0 96.0 96.0 0.95 0.90
121.0 B125 105.0 121.0 121.0 0.95 0.90
146.0 B150 127.0 145.0 145.0 0.95 0.90
193.0 B200 167.0 192.0 192.0 0.95 0.90

Amps Out Drive Rating kVA Out 500 Vac kVA Out 575 Vac kVA Out 600 Vac Internal Chassis Component Heat Dissipation (BTU/HR) (n) Heatsink Heat Dissipation (BTU/HR) (n) Total Dissipation (BTU/HR) (n) Min CFM Req (n)
4.3 B003 3.7 4.3 4.3 136 239 375 15
6.7 B005 5.8 6.7 6.7 171 307 477 25
9.9 B007 8.6 9.9 9.9 273 444 717 40
12.1 B010 10.5 12.1 12.1 341 512 853 45
19.0 B015 16.5 18.9 18.9 443 853 1296 60
24.0 B020 20.8 23.9 23.9 477 1023 1500 80
30.0 B025 26.0 29.9 29.9 614 1364 1978 105
35.0 B030 30.3 34.9 34.9 716 1535 2251 115
45.0 B040 39.0 44.8 44.8 938 1876 2814 145
57.0 B050 49.4 56.8 56.8 1125 2217 3342 175
85.0 B075 73.6 84.7 84.7 1705 4433 6138 320
109.0 B100 94.4 108.6 108.6 2046 5797 7843 405
138.0 B125 119.5 137.4 137.4 2387 6820 9207 475
158.0 B150 136.8 157.4 157.4 2728 5825 11253 580
210.0 B200 181.9 209.1 209.1 3069 10571 13640 703

(n) The above information is provided for reference only. For all ratings the user must verify that the selected enclosure will dissipate the total BTUs generated within the enclosure without allowing the internal ambient to rise above 50°C. Enclosure mounting and location must allow for the heatsink to extend outside the enclosure.

. When locating the drive allow a minimum clearance from other components of 4.0 inches (101.6 mm) on the top and bottom, 2.0 inches (50.8 mm) on either side.

. When mounting the drive, ensure that the heatsink fins are vertical. With the heatsink exposed to the ambient, the drive will dissipate heat as listed in the Output Current Table above.