Drives Service & Support
0 to 575V AC (maximum output voltage cannot exceed applied input voltage).
Input Current and kVA
Output Current and kVA
| Amps In |
Rating Code |
kVA In 500 Vac |
kVA In 575 Vac |
kVA In 600 Vac |
Input Power Factor Displacement Angle |
kW/kVA |
| 3.2 |
B003 |
2.8 |
3.2 |
3.2 |
0.95 |
0.85 |
| 5.1 |
B005 |
4.4 |
5.1 |
5.1 |
0.95 |
0.85 |
| 7.7 |
B007 |
6.7 |
7.7 |
7.7 |
0.95 |
0.85 |
| 10.2 |
B010 |
8.9 |
10.2 |
10.2 |
0.95 |
0.85 |
| 15.0 |
B015 |
13.0 |
15.0 |
15.0 |
0.95 |
0.90 |
| 19.0 |
B020 |
17.0 |
19.0 |
19.0 |
0.95 |
0.90 |
| 24.0 |
B025 |
21.0 |
24.0 |
24.0 |
0.95 |
0.90 |
| 29.0 |
B030 |
25.0 |
29.0 |
29.0 |
0.95 |
0.90 |
| 39.0 |
B040 |
33.0 |
38.0 |
38.0 |
0.95 |
0.90 |
| 48.0 |
B050 |
42.0 |
48.0 |
48.0 |
0.95 |
0.90 |
| 73.0 |
B075 |
63.0 |
73.0 |
73.0 |
0.95 |
0.90 |
| 97.0 |
B100 |
84.0 |
96.0 |
96.0 |
0.95 |
0.90 |
| 121.0 |
B125 |
105.0 |
121.0 |
121.0 |
0.95 |
0.90 |
| 146.0 |
B150 |
127.0 |
145.0 |
145.0 |
0.95 |
0.90 |
| 193.0 |
B200 |
167.0 |
192.0 |
192.0 |
0.95 |
0.90 |
| Amps Out |
Drive Rating |
kVA Out 500 Vac |
kVA Out 575 Vac |
kVA Out 600 Vac |
Internal Chassis Component Heat Dissipation (BTU/HR) (n) |
Heatsink Heat Dissipation (BTU/HR) (n) |
Total Dissipation (BTU/HR) (n) |
Min CFM Req (n) |
| 4.3 |
B003 |
3.7 |
4.3 |
4.3 |
136 |
239 |
375 |
15 |
| 6.7 |
B005 |
5.8 |
6.7 |
6.7 |
171 |
307 |
477 |
25 |
| 9.9 |
B007 |
8.6 |
9.9 |
9.9 |
273 |
444 |
717 |
40 |
| 12.1 |
B010 |
10.5 |
12.1 |
12.1 |
341 |
512 |
853 |
45 |
| 19.0 |
B015 |
16.5 |
18.9 |
18.9 |
443 |
853 |
1296 |
60 |
| 24.0 |
B020 |
20.8 |
23.9 |
23.9 |
477 |
1023 |
1500 |
80 |
| 30.0 |
B025 |
26.0 |
29.9 |
29.9 |
614 |
1364 |
1978 |
105 |
| 35.0 |
B030 |
30.3 |
34.9 |
34.9 |
716 |
1535 |
2251 |
115 |
| 45.0 |
B040 |
39.0 |
44.8 |
44.8 |
938 |
1876 |
2814 |
145 |
| 57.0 |
B050 |
49.4 |
56.8 |
56.8 |
1125 |
2217 |
3342 |
175 |
| 85.0 |
B075 |
73.6 |
84.7 |
84.7 |
1705 |
4433 |
6138 |
320 |
| 109.0 |
B100 |
94.4 |
108.6 |
108.6 |
2046 |
5797 |
7843 |
405 |
| 138.0 |
B125 |
119.5 |
137.4 |
137.4 |
2387 |
6820 |
9207 |
475 |
| 158.0 |
B150 |
136.8 |
157.4 |
157.4 |
2728 |
5825 |
11253 |
580 |
| 210.0 |
B200 |
181.9 |
209.1 |
209.1 |
3069 |
10571 |
13640 |
703 |
(n) The above information is provided for reference only. For all ratings the user must verify that the selected enclosure will dissipate the total BTUs generated within the enclosure without allowing the internal ambient to rise above 50°C. Enclosure mounting and location must allow for the heatsink to extend outside the enclosure.