The Allen-Bradley 1321 Isolation Transformers are designed to meet
the standard horsepower, voltage ratings and harmonics of the Allen-
Bradley variable speed drives.
| Electrical |
| |
Delta primary, wye secondary |
| 60 Hz |
| Aluminum wound |
| Neutral terminal available for customer use |
| Standard Voltage Taps |
- 7.5-175 kVA 1-5.0% FCAN & FCBN
- 220-880 kVA 1-2.5% FCAN & FCBN
|
| Insulation System |
- Class 220
- 150 degrees C Rise Over 40 degrees C Ambient
- Peak 40 degrees C Ambient with 30 degrees C 24 Hour Avg.
|
| Environmental |
| Elevation |
Up to 1,000 Meters. Above 1,000 Meters consult factory for derating |
| U.L. Listed |
File E112313 |
| CSA Certified |
File LR3902 |
| Construction |
| Enclosure |
NEMA Type 3R (IP32)
Heavy duty ventilated enclosure with metal screens protecting all
vents and finished in ANSI 61 grey |
| Termination |
Transformers up to 75kVA have integral high and low voltage lugs
installed, suitable for copper or aluminum cable installation |
| Conduit Entry |
Standard knockouts on units up to 175 kVA. |
| Mounting |
5-51 kVA units suitable for either floor or wall mounting. 63-75 kVA
units suitable for floor, wall or ceiling mounting with mounting kit
1321-3TWM2 (Style NH3). Larger units are floor mount only |
| General |
| Impedance |
4-6% impedance (nominal). |
| Short Circuit Capability |
Meets UL and CSA short circuit withstand capability. |
| Overload Rating |
Windings designed to withstand overcurrent of 150% of rated load
for 60 Seconds or 200% of rated load for 30 Seconds. |
| Duty Cycle |
(1) start every (2) hours. |
| Thermostats |
Thermostats with 1 N.C contact in each coil, wired in series and
integral on all units |
| K Factor |
4 |
| Custom Options |
| |
50Hz units. |
| Electrostatic shield (60dB attenuation typical). |
| Core and coil construction (open). |
| Additional HP or kVA sizes, voltages, extra primary taps, copper wound units, etc. |