Material
Terminations Tin-plated copper. All terminals have terminal designation (L1, L2,
L3, etc.) stamped on them.
Mounting Attitude Mounting on subpanel or floor of cabinet. Four (4) holes are provided
for mounting on a flat surface. Holes are sized for 1/4" bolts.
Electrical
Inductance Inductance to be determined by shorting together L4-L5-L6 and
testing for 50 or 60Hz inductive reactance at rated current by a
separate balanced and adjustable 3-phase voltage source
connected to L1, L2 & L3.
Insulation System Class H (180 degrees C or better).
Construction Core and coils vacuum impregnated and baked.
Environmental
Ambient Temperature 60 degrees C maximum, 0 degrees C minimum.
Altitude Maximum altitude 1000 meters (3281 feet).
Relative Humidity 5 to 95% non-condensing.
Cooling Natural convection.
Rating Insulation materials U.L. Recognized. Spacing complies with UL-
508 Table 47.1 Column A and CSA C22.2 No. 14-M1987 Table 6
Group A.