Drives Service & Support

General Resources

     

Drives Service & Support > Powerflex 4 > Drive Ratings

Click for Dimensions
Click for Specifications

Catalog Number
Output Ratings
Input Ratings
Branch Circuit Protection
Power
Dissipation
kW (HP)
Amps
Voltage
Range
kVA
Amps
Fuses
140M Motor
 Protectors
Contactors
IP20 Open
Watts
100-115V AC 1-Phase Input, 0-230V 3-Phase Output
22A-V1P5N104
0.2 (0.25)
1.5
90-126
0.75
6.0
10
140M-C2E-C10
100-C09
25
22A-V2P3N104
0.37 (0.5)
2.3
90-126
1.15
9.0
15
140M-C2E-C16
100-C12
30
22A-V4P5N104
0.75 (1.0)
4.5
90-126
2.25
18.0
30
140M-D8E-C20
100-C23
50
200 - 240V AC – 1-Phase(1) Input, 0- 230V 3-Phase Output
22A-A1P5N104
0.2 (0.25)
1.5
180-265
0.75
5.0
10
140M-C2E-B63
100-C009
25
22A-A2P3N104
0.37 (0.5)
2.3
180-265
1.15
6.0
10
140M-C2E-B63
100-C009
30
22A-A4P5N104
0.75 (1.0)
4.5
180-265
2.25
10.0
15
140M-C2E-C16
100-C12
50
22A-A8P0N104
1.5 (2.0)
8.0
180-265
4.0
18.0
30
140M-D8E-C20
100-C23
80
200 - 240V AC – 3-Phase Input, 0 - 230V 3-Phase Output
22A-B1P5N104
0.2 (0.25)
1.5
180-265
0.75
1.8
3
140M-C2E-B25
100-C09
25
22A-B2P3N104
0.37 (0.5)
2.3
180-265
1.15
2.5
6
140M-C2E-B40
100-C09
30
22A-B4P5N104
0.75 (1.0)
4.5
180-265
2.25
5.2
10
140M-C2E-C10
100-C09
50
22A-B8P0N104
1.5 (2.0)
8.0
180-265
4.0
9.5
15
140M-C2E-C16
100-C12
80
22A-B012N104
2.2 (3.0)
12.0
180-265
5.5
15.5
25
140M-C2E-C16
100-C16
115
22A-B017N104
3.7 (5.0)
17.5
180-265
8.6
21.0
35
140M-F8E-C25
100-C23
165
380 - 480V AC – 3-Phase Input, 0 - 460V 3-Phase Output
22A-D1P4N104 0.37 (0.5) 1.4 340-528 1.4 1.8 3 140M-C2E-B25 100-C09 30
22A-D2P3N104 0.75 (1.0) 2.3 340-528 2.3 3.2 6 140M-C2E-B40 100-C09 40
22A-D4P0N104 1.5 (2.0) 4.0 340-528 4.0 5.7 10 140M-C2E-B63 100-C09 60
22A-D6P0N104 2.2 (3.0) 6.0 340-528 5.9 7.5 15 140M-C2E-C10 100-C09 90
22A-D8P7N104 3.7 (5.0) 8.7 340-528 8.6 9.0 15 140M-C2E-C16 100-C16 145

(1) 200-240V AC - 1-Phase drives are also available with an integral EMC filter. Catalog suffix changes from N104 to N114.

Input / Output Ratings Output Frequency 0-240hz (Programmable)
Efficiency 97.5% (Typical)
Approvals
Digital Control Inputs SRC (Source) Mode 18-24V = ON
0-6V = OFF
SNK (Sink) Mode 0-6V = ON
18-24V = OFF
Analog Control Inputs 4-20mA Analog 250 Ohm Input Impedance
0-10V DC Analog 100k Ohm Input Impedance
External Pot 1-10k ohms, 2 Watt Minimum
Control Output
Programmable Output (form C relay)
Resistive Rating 3.0A at 30Vdc/125Vac/240Vac
Inductive Rating 0.5A at 30Vdc/125Vac/240Vac
Protective Features Motor Protection I2T Overload Protection - 150% for 60 Seconds, 200% for 3 Seconds (Provides Class 10 Protection)
Over Current 200% Hardware Limit
300% Instantaneous Fault
Over Voltage 100-120Vac Input - Trip at 405Vdc Bus Voltage (Equivalent to 150Vac Incoming Line)
200-240Vac Input - Trip at 405Vdc Bus Voltage (Equivalent to 290Vac Incoming Line)
380-480Vac Input - Trip at 810Vdc Bus Voltage (Equivalent to 575Vac Incoming Line)
Under Voltage 100-120Vac Input - Trip at 210Vdc Bus Voltage (Equivalent to 75Vac Incoming Line)
200-240Vac Input - Trip at 210Vdc Bus Voltage (Equivalent to 150Vac Incoming Line)
380-480Vac Input - Trip at 390Vdc Bus Voltage (Equivalent to 275Vac Incoming Line)
Control Ride Through Minimum Ride Through is 0.5 Seconds, Typical Value 2 Seconds
Faultless Power Ride Through 100 milliseconds
Dynamic Braking Internal brake IGBT included with all ratings (except no brake version)

Back to top