Drives Service & Support
NOTE: Unshielded cable refers to bundled cable and not random wires in a tray. Shielded cable is Belden series 295xx or equivalent.
PowerFlex 40, 400V Shielded/Unshielded Cable - Feet
| Rating |
No Solution |
Reactor Only |
Reactor + Damping Resistor |
Reactor/RWR |
Resistor |
Used with |
| kW |
kHz |
1000V |
1200V |
1488V |
1600V |
1000V |
1200V |
1488V |
1600V |
1000V |
1200V |
1488V |
1600V |
Catalog No. |
Ohms |
Watts |
TFA1 |
TFB2 |
RWR2 |
RWC |
| 0.4 |
2/4 |
25 |
175 |
175 |
175 |
300 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
|
|
|
X |
|
X |
X |
| 0.75 |
2/4 |
25 |
275 |
275 |
275 |
300 |
500 |
500 |
500 |
500 |
500 |
500 |
500 |
|
|
|
X |
|
X |
X |
| 1.5 |
2/4 |
25 |
275 |
275 |
275 |
300 |
500 |
500 |
500 |
500 |
500 |
500 |
500 |
|
|
|
X |
X |
X |
X |
| 2.2 |
2/4 |
25 |
450 |
600 |
600 |
300 |
600 |
600 |
600 |
600 |
600 |
600 |
600 |
1321-RWR8-DP |
|
|
X |
X |
X |
X |
| 4 |
2/4 |
25 |
450 |
800 |
800 |
300 |
800 |
800 |
800 |
800 |
800 |
800 |
800 |
1321-RWR12-DP |
|
|
X |
X |
|
X |
| 5.5 |
2/4 |
25 |
450 |
1000 |
1000 |
300 |
1000 |
1000 |
1000 |
1000 |
1000 |
1000 |
1000 |
1321-RWR12-DP |
|
|
|
X |
|
X |
| 7.5 |
2/4 |
25 |
450 |
1200 |
1200 |
300 |
1200 |
1200 |
1200 |
1200 |
1200 |
1200 |
1200 |
1321-RWR18-DP |
|
|
|
X |
|
X |
| 11 |
2/4 |
25 |
450 |
1200 |
1200 |
300 |
1200 |
1200 |
1200 |
1200 |
1200 |
1200 |
1200 |
1321-RWR25-DP |
|
|
|
X |
|
|
PowerFlex 40, 480V Shielded/Unshielded Cable - Feet
| Rating |
No Solution |
Reactor Only |
Reactor + Damping Resistor |
Reactor/RWR |
Resistor |
Used with |
| HP |
kHz |
1000V |
1200V |
1488V |
1600V |
1000V |
1200V |
1488V |
1600V |
1000V |
1200V |
1488V |
1600V |
Catalog No. |
Ohms |
Watts |
TFA1 |
TFB2 |
RWR2 |
RWC |
| 0.5 |
2/4 |
25 |
40 |
175 |
175 |
25 |
300 |
400 |
400 |
400 |
400 |
400 |
400 |
|
|
|
X |
|
X |
X |
| 1 |
2/4 |
25 |
40 |
275 |
275 |
25 |
300 |
500 |
500 |
500 |
500 |
500 |
500 |
|
|
|
X |
|
X |
X |
| 2 |
2/4 |
25 |
40 |
275 |
275 |
25 |
300 |
600 |
600 |
600 |
600 |
600 |
600 |
|
|
|
X |
X |
X |
X |
| 3 |
2/4 |
25 |
40 |
425 |
425 |
25 |
300 |
600 |
600 |
600 |
600 |
600 |
600 |
1321-RWR8-DP |
|
|
X |
X |
X |
X |
| 5 |
2/4 |
25 |
40 |
450 |
600 |
25 |
300 |
800 |
800 |
600 |
800 |
800 |
800 |
1321-RWR12-DP |
|
|
X |
X |
|
X |
| 7.5 |
2/4 |
25 |
40 |
450 |
600 |
25 |
300 |
1000 |
1000 |
600 |
1000 |
1000 |
1000 |
1321-RWR12-DP |
|
|
|
X |
|
X |
| 10 |
2/4 |
25 |
40 |
450 |
600 |
25 |
300 |
1200 |
1200 |
600 |
1200 |
1200 |
1200 |
1321-RWR18-DP |
|
|
|
X |
|
X |
| 15 |
2/4 |
25 |
40 |
450 |
600 |
25 |
300 |
1200 |
1200 |
600 |
1200 |
1200 |
1200 |
1321-RWR25-DP |
|
|
|
X |
|
|
PowerFlex 40, 600V Shielded/Unshielded Cable - Feet
| Rating |
No Solution |
Reactor Only |
Reactor + Damping Resistor |
Reactor/RWR |
Resistor |
Used with |
| HP |
kHz |
1488V |
1850V |
1488V |
1850V |
1488V |
1850V |
Catalog No. |
Ohms |
Watts |
TFA1 |
TFB2 |
RWR2 |
RWC |
| 1 |
2/4 |
140 |
400 |
400 |
400 |
400 |
400 |
|
|
|
X |
|
X |
X |
| 2 |
2/4 |
140 |
500 |
500 |
500 |
500 |
500 |
|
|
|
X |
|
X |
X |
| 3 |
2/4 |
140 |
500 |
500 |
500 |
600 |
600 |
|
|
|
X |
|
X |
X |
| 5 |
2/4 |
140 |
500 |
500 |
800 |
800 |
800 |
1321-RWR8-DP |
|
|
X |
X |
X |
X |
| 7.5 |
2/4 |
140 |
600 |
500 |
1000 |
1000 |
1000 |
1321-RWR12-DP |
|
|
|
X |
|
X |
| 10 |
2/4 |
140 |
600 |
500 |
1200 |
1200 |
1200 |
1321-RWR18-DP |
|
|
|
X |
|
X |
| 15 |
2/4 |
140 |
600 |
500 |
1200 |
1200 |
1200 |
1321-RWR25-DP |
|
|
|
X |
|