Drives Service & Support
Fault Number : 2
Fault Display : Auxiliary Input
Fault Name : Auxiliary Input
Fault Type : 1 - Auto-Reset Run
Fault Description : Auxiliary input interlock is open
Corrective Action : All I/O terminals are programmable by using parameters 361 to parameters 366 [Digital In 1-6 Sel]. If any of these parameters are programmed to a value of 3 "Aux Fault", a true connection is required at those terminals. If they are programmed as an Aux Fault, and the terminal is not set for a true condition, then the drive will fault out with this fault. No input is programmed for Aux Fault by default.
|