Allen-Bradley Home
Drives Service & Support

General Resources

Drives Service & Support > PowerFlex 70 > Fault Finder

Fault Number : 111

Fault Display : Enable Hardware

Fault Name : Enable Hardware

Fault Type : None

Fault Description : Safe-Off board is not installed and pins 3 and 4 of the Safe-Off Connector are not jumpered. OR Safe-Off board has failed. OR Hardware enable circuitry failed.

Corrective Action : Check to make sure that pins 3 and 4 of the Safe-Off connector are properly jumpered.

 


Support Options