| Drives Service & Support
Auto/Manual Application User Supplied 115 AC volt Logic power
Note:
Auto = Speed reference from DPI Port 1 (HIM)
Manual = Speed reference from Speed Pot
Parameters that need to be reprogrammed
File - Utility
Goup - Drive Memory
196 (Param Access Lvl) = 1 (Advanced)
File - Speed Command
Group - Speed References
96 (TB Man Ref Sel) = 2 (Analog In 2)
90 (Speed Ref A Sel) = 18 (DPI Port 1)
File - Speed Command
Group - Speed Trim
117 (Trim In Select) = 20 (DPI Port 3)
File - Speed Command
Group - Process PI
128 (PI Feedback Sel) = 20 (DPI Port 3)
File - Inputs & Outputs
Group - Digital Inputs
366 (Digital In6 Sel) = 18 (Auto/Manual)

|