Selecting 2 Different Acc/Dec Rates

Parameters that need to be reprogrammed
File - Inputs & Outputs
Group - Digital Inputs

361 (Digital In1 Sel) = 4
362 (Digital In2 Sel) = 5
363 (Digital In3 Sel) = 10
364 (Digital In4 Sel) = 15
365 (Digital In5 Sel) = 21
366 (Digital In6 Sel) = 22

Example of Accel & Decel Times
File - Dynamic Control
Group - Ramp Rates

140 (Accel Time 1) = 10 sec
141 (Accel Time 2) = 1 Sec
142 (Decel Time 1) = 10 Sec
143 (Decel Time 2) = 1 Sec