| Category |
Specification |
| |
380/400V |
480V |
600V |
690V |
| Protection |
| Bus Overvoltage Trip |
911V DC |
911V DC |
1200V DC |
1200V DC |
| Bus Undervoltage Shutoff/Fault |
333V DC |
333V DC |
461V DC |
461V DC |
| Heat Sink Thermistor |
Monitored by microprocessor overtemp trip |
| Ground Fault Protection |
Yes |
| Input Phase Loss Protection |
Yes |
| Input Overcurrent Protection |
Yes |
| Overtemperature Protection |
Yes |
| LCL Filter Overtemperature Protection |
Yes |
| Line Transients |
Up to 6000 volts peak per IEEE C62.41-1991 |
| Control Logic Noise Immunity |
Showering arc transients up to 1500V peak |
| Ground Fault Trip |
DC bus-to-ground current exceeds par 082 [Ground I Lvl] value |
| Environment |
| Altitude |
1000 m (3300 ft) max. without derating |
| Max. Surrounding Air Temp w/o Derating |
0 to 40°C (32 to 104°F) |
| Storage Temperature (all const) |
–40 to 60°C (–40 to 140°F) |
| Atmosphere |
Important: The AFE must not be installed in an area where
the ambient atmosphere contains volatile or corrosive gas,
vapors or dust. If the AFE is not going to be installed for a
period of time, it must be stored in an area where it will not be
exposed to a corrosive atmosphere. |
| Relative Humidity |
5 to 95% non-condensing |
| Shock (Non-Operational) |
15G peak for 11 ms duration
EN50178 / EN60068-2-27 |
| Vibration |
1 mm (0.039 in.) displacement, 1G peak
EN50178 / EN60068-2-6 |
| Sound Frame 10 |
71 dB at 1 m (3.28 ft.) |
| Sound Frame 13 |
80 dB at 1 m (3.28 ft.) |
| Electrical |
| AC Input Voltage Tolerance: |
±10% |
| Frequency Tolerance: |
48-63 Hz. |
| Input Phases: |
Three-phase input provides full rating for all AFEs. The AFE
cannot be operated with single-phase input. |
| Displacement Power Factor: |
1.0 default across entire range. |
| Efficiency: |
97.5% at rated amps, nominal line volts. |
| Short Circuit Rating: |
Determined by AIC rating of installed fuse/circuit breaker. |
| Control |
| DC Output Voltage Range |
462-702 |
583-842 |
700-932 |
802-1071 |
| Method |
Sine-coded PWM |
| Carrier Frequency |
3.6 kHz |
| Normal Duty Intermittent Overload |
110% Overload capability for up to 1 minute |
| Heavy Duty Intermittent Overload |
150% Overload capability for up to 1 minute |
| Current Limit Capability |
Current Limit programmable from 20 to 150% of rated input current. |