  Drives Service & Support > PowerFlex 700L > Specifications

Specifications current as of 7/2006

  Frame 3B Frames 3A & 3B
  400V 480V 600V 690V
AC Input Overvoltage Trip 528V 528V 760V 760V
AC Input Undervoltage Trip 340V 340V 340V 340V
Bus Overvoltage Trip 815V 815V 1168V 1168V
Bus Undervoltage Shutoff 300V 300V 300V 300V
Nominal Bus Voltage 600V 700V 900V 1000V
Heatsink Thermistor
Monitored by microprocessor overtemp trip
Drive Overcurrent Trip
Software Overcurrent Trip
200% of rated current (Typical)
Hardware Overcurrent Trip
220-300% of rated current
(depending on drive rating)
Line Transients
Up to 6000 volts peak per IEEE C62.41-1991
Control Logic Noise Immunity
Showering Arc transients up to 1550V peak
Logic Control Ride Thru
Vector Contol
0.5 Seconds minimum, 2 seconds typical
700S Phase II Control
0.25 seconds, drive not running
Ground Fault Trip
Phase to ground on drive output
Short Circuit Trip
Phase to phase on drive output

 

Environment  Altitude 1000 m (3300 ft) max. without derating
Max Surrounding Air Temperature without Derating (NEMA Type 1, IP21) 0 to 40°C (32 to 104°F)
Storage Temperature –40 to 85°C (–40 to 185°F)
Atmosphere Important: Drive must not be installed in an area where the ambient atmosphere contains volatile or corrosive gas, vapors or dust. If the drive is not going to be installed for a period of time, it must be stored in an area where it will not be exposed to a corrosive atmosphere.
Relative Humidity 5 to 95% non-condensing
Shock 10G peak for 11ms duration (+/- 1.0 ms)
Vibration 0.152 mm (0.006in.) displacement, 1G peak, 5.5hz
     
Electrical Voltage Tolerance
Vector Control For full power and operating range, see the PowerFlex 700 Adjustable Frequency AC Drive — Series B User Manual (Publication No. 20B-UM002…), Appendix C.
700S Phase II Control For full power and operating range, see the PowerFlex 700S High Performance AC Drive — Phase II Control User Manual (Publication No. 20D-UM006…), Appendix C.
Frequency Tolerance 27 - 93 hz
Input Phases Three-phase input provides full rating for all drives. Single-phase operation provides 50% of rated current
Displacement Power Factor 0.98 across entire speed range
Efficiency 97.5% at rated amps, nominal line volts
Maximum short circuit current rating To match specified circuit breaker capability ≤
200,000 Amps
Actual short circuit rating Determined by AIC rating of installed circuit breaker
Motor Lead Lengths 76 meters (250 feet) total

 

     
Control   Method Sine coded PWM with programmable carrier frequency. Ratings apply to all drives (refer to the Derating Guidelines in the PowerFlex Reference Manual).
Carrier Frequency 2 or 4 khz. Drive rating based on 4 khz
Output Voltage Range 0 to rated motor voltage
Output Frequency Range
Vector Control 0 to 420 hz
700S Phase II Control 0 to 350 hz
Frequency Accuracy (Vector Control Only)
Digital Input Within ± 0.01% of set output frequency.
Analog Input Within ± 0.4% of maximum output frequency.
Frequency Control (Vector Control Only)
Speed Regulation - w/Slip Compensation (Volts per Hertz Mode) 0.5% of base speed across 40:1 speed range
40:1 operating range
10 rad/sec bandwidth
Speed Regulation - w/Slip Compensation (Sensorless Vector Mode) 0.5% of base speed across 80:1 speed range
80:1 operating range
20 rad/sec bandwidth
Speed Regulation - w/Feedback (Sensorless Vector Mode) 0.1% of base speed across 80:1 speed range
80:1 operating range
20 rad/sec bandwidth
Speed Control
Vector Control Speed Regulation - without feedback (Vector Control Mode)
0.1% of base speed across 120:1 speed range
120:1 operating range
50 rad/sec bandwidth
Speed Regulation - with feedback (Vector Control Mode)
0.001% of base speed across 120:1 speed range
1000:1 operating range
250 rad/sec bandwidth
700S Phase II Control Speed Regulation - without feedback
0.1% of base speed across 120:1 speed range
120:1 operating range
50 rad/sec bandwidth
Speed Regulation - with feedback
0.001% of base speed across 120:1 speed range
1000:1 operating range
740 rad/sec bandwidth
Torque Regulation
Vector Control Torque regulation without Feedback; ± 5%, 600 rad/sec bandwidth
Torque regulation with Feedback; ± 2%, 2500 rad/sec bandwidth
700S Phase II Control Torque regulation without Feedback; ± 10%, 600 rad/sec bandwidth
Torque regulation with Feedback; ± 5%, 4400 rad/sec bandwidth
Selectable Motor Control
Vector Control Sensorless Vector with full tuning. Standard V/Hz with full custom capability and Vector Control with Force Technology (with and without feedback).
700S Phase II Control Vector Control with Force Technology (with and without feedback), V/Hz Control, and permanent magnet motor control.
Stop Modes
Vector Control Multiple programmable stop modes including Ramp, Coast, DC-Brake, Ramp-to-Hold, and S-curve.
700S Phase II Control Multiple programmable stop modes including Ramp, Coast, and Current Limit.
Accel / Decel
Vector Control Two independently programmable accel and decel times. Each time may be programmed from 0-3600 seconds in 0.1 second increments.
700S Phase II Control Independently programmable accel and decel times, adjustable from 0-6553.5 seconds in 0.01 second increments.
Intermittent Overload 110% Overload capability for up to 1 minute
150% Overload capability for up to 3 seconds
Current Limit Capability  
Vector Control Proactive Current Limit programmable from 20 to 160% of rated output current. Independently programmable proportional and integral gain.
700S Phase II Control Independent Motoring and Regenerative Power Limits programmable to 800% of rated output current.
Electronic Motor Overload Protection Class 10 protection with speed sensitive response. Investigated by U.L. to comply with N.E.C. Article 430. U.L. File E59272, volume 12.

 

Encoder
(Vector Control Only)
Type Incremental, dual channel
Supply 12V or 5V, 250 mA. 12V or 5V, 10 mA minimum inputs isolated with differential transmitter, 250 kHz maximum.
Quadrature 90°, ± 27° at 25°C
Duty Cycle 50%, ± 10%
Requirements Encoders must be line driver type, quadrature (dual channel) or pulse (single channel), 8-15V DC output (3.5-6V DC for 5V encoder),
single-ended or differential, and capable of supplying a minimum of 10 mA per channel. Maximum input frequency is 250 kHz. The Encoder Interface Board accepts 12V DC or 5V DC square-wave with a minimum high state of 7.0V DC (12 volt encoder) or 3.1V DC (5 volt encoder). Maximum low state voltage is 0.4V DC.
     
Feedback
(700S Phase II Control Only)
Encoder Input Dual Channel Plus Marker, Isolated with differential transmitter Output (Line Drive) Incremental, Dual Channel Quadrature type
Encoder Voltage Supply 5V DC or 12V DC (5V DC requires an external power supply),
320 mA/channel
Maximum Input Frequency 400 kHz
Stegmann Hi-Resolution Option
Encoder Voltage Supply 11.5V DC @ 130 mA
Hi-Resolution Feedback Sine/Cosine 1V P-P Offset 2.5
Maximum Cable Length 182 m (600 ft.)
RS-485 Interface Hi-Resolution Feedback Option card obtains the following information via the Hiperface RS-485 interface shortly after power-up: Address, Command Number, Mode, Number of Turns, Number of Sine/Cos cycles, and Checksum.
Customer-I/O Plug (P1) - Hi Res Allen-Bradley PN: S94262912
Weidmuller PN: BL3.50/90/12BK
Resolver Option
Excitation Frequency 2400 Hz
Excitation Voltage 4.25-26 Vrms
Operating Frequency Range 1-10 kHz
Resolver Feedback Voltage 2V ± 300mV
Maximum Cable Length 304.8 m (1000 ft.)
     
DriveLogix
(700S Phase II Control Only)
User Available Memory Base 1.5 megabytes
Battery 1756-BA1 (Allen-Bradley P/N 94194801) 0.59g lithium
Serial Cable 1761-CBLPM02 to 1761-NET-AIC
1761-CBLPA00 to 1761-NET-AIC
1756-CP3 directly to controller
1747-CP3 directly to controller
Category 3 (2)
Compact I/O Connection Up to (30) modules
Cable 20D-DL2-CL3
20D-DL2-CR3