| Category |
Specification |
200-208V
Drive |
240V
Drive |
380/400V
Drive |
480V
Drive |
600V
Drive |
690V
Drive |
| Protection |
AC Input Overvoltage Trip: |
247VAC |
285VAC |
475VAC |
570VAC |
690VAC |
- |
| Bus Overvoltage Trip: |
350VDC |
405VDC |
675VDC |
810VDC |
1013VDC |
- |
| Bus Undervoltage Trip: |
Adjustable |
| Nominal Bus Voltage: |
281VDC |
324VDC |
540VDC |
648VDC |
810VDC |
- |
| Heat Sink Thermistor: |
Monitored by microprocessor overtemp trip |
Drive Overcurrent Trip |
| Software Current Limit: |
Calculated value, 105% of motor rated to 200% of drive rated |
| Hardware Current Limit: |
105% of 3 sec. rating (158%-210%) |
| Instantaneous Current Limit: |
143% of 3 sec rating (215%-287%) |
|
| Line Transients: |
Up to 6000 volts peak per IEEE C62.41-1991 |
| Control Logic Noise Immunity: |
Showering arc transients up to 1500V peak |
| Power Ride-Thru: |
15 milliseconds at full load |
| Logic Control Ride-Thru |
0.25 sec., drive not running |
| Ground Fault Trip: |
Phase-to-ground on drive output |
| Short Circuit Trip: |
Phase-to-phase on drive output |
Agency
Certification |
The drive is designed to meet the following specifications:
- NFPA 70 – US National Electric Code
- NEMA ICS 3.1 – Safety Standards for Construction and Guide for Selection, Installation and Operation of Adjustable Speed Drive Systems.
- NEMA 250 – Enclosures for Electrical Equipment
- IEC 146 – International Electrical Code.
|
 |
UL and cUL Listed to UL508C and CAN/CSA-C2.2 No. 14-M91 |
 |
Marked for all applicable European Directives
EMC Directive (89/336/EEC)
Emissions
EN 61800-3 Adjustable Speed electrical power drive systems Part 3
Immunity
EN 61800-3 Second Environment, Restricted Distribution
Low Voltage Directive (73/23/EEC)
EN 50178 Electronic Equipment for use in Power Installations |
| Category |
Specification |
| Environment |
Altitude: |
1000 m (3300 ft.) max. without derating |
Surrounding Air Temperature without
Derating: |
Open Type: 0 to 50° C (32 to 122° F)
IP20: 0 to 50° C (32 to 122° F)
NEMA Type 1: 0 to 40° C (32 to 104 ° F)
IP56, NEMA Type 4X: 0 to 40 ° C (32 to 104 ° F) |
| Storage Temperature (all const.): |
-40 to 70° C (-40 to 158° F) |
| Relative Humidity: |
5 to 95% non-condensing |
| Shock: |
10G peak for 11 ms duration (+/- 1.0 ms) |
| Vibration: |
0.152 mm (0.006 in.) displacement, 1G peak |
| Electrical |
Voltage Tolerance: |
- 10% of minimum, + 10% of maximum. |
| Frequency Tolerance: |
47-63 Hz |
| Input Phases: |
Three-phase input provides full rating for all drives. Single-phase operation provides 50% of rated current. |
| DC Input Voltage Tolerance |
+/- 10% of Nominal Bus Voltage (above) |
| Displacement Power Factor: |
0.98 across speed range |
| Displacement Power Factor |
0.98 across speed range |
| Efficiency: |
97.5% at rated amps, nominal line volts. |
Max. Short Circuit Current Rating:
Using Recommended Fuse or Circuit
Breaker Type |
Maximum short circuit current rating to match specified fuse/circuit breaker capability.
< / = 200,000 Amps |
| Maximum Drive to Motor Power Ratio |
The drive to motor rating cannot exceed a 2:1 ratio |
| Control |
Method
Induction Motor:
Brushless Motor: |
Ratings apply to all drives (refer to the Derating Guidelines). The drive can be supplied as 6 pulse or 12 pulse
in a configured package. Indirect Self-Organized, Field-Oriented Control Current-regulated, sine-coded PWM
with programmable carrier frequency |
Carrier Frequency
Frames 0 - 4 |
Drive rating: 4 kHz, Settings: 2, 4, 8, 10 kHz |
| Output Voltage Range: |
0 to rated motor voltage |
| Output Frequency Range: |
0 – 320 Hz |
| Speed Regulation |
| Without Feedback |
0.1% of base speed across 120:1 speed range
120:1 operating range
50 rad/sec bandwidth |
| With Feedback |
0.001% of base speed across 120:1 speed range
1000:1 operating range
300 rad/sec bandwidth |
|
| Torque Regulation |
| Without Feedback |
+/-10%, 600 rad/sec bandwidth |
| With Feedback |
+/-5%, 2500 rad/sec bandwidth |
|
| Selectable Motor Control: |
Field Oriented Control with and without a feedback device and Brushless motor control |
| Stop Modes: |
Multiple programmable stop modes including – Ramp, Coast and Current Limit |
| Accel/Decel |
Independently programmable accel and decel times adjustable
from 0 to 6553.5 in 0.1 second increments. |
| S-Curve Time |
Adjustable from 0.5 to 4.0 seconds |
| Intermittent Overload |
110% Overload capability for up to 1 minute
150% Overload capability for up to 3 seconds |
| Current Limit Capability: |
Independent Motoring and Regenerative Power Limits programmable to 800% of rated output current |
| Electronic Motor Overload Protection |
Class 10 protection with speed sensitive response. Investigated by U.L. to comply with N.E.C. Article 430 U.L.
File E59272, volume 12. |
| Feedback |
Encoder Inputs |
Dual Channel Plus Marker, Isolated with differential transmitter
Output (Line Drive) Incremental, Dual Channel Quadrature type |
| Encoder Voltage Supply |
5V DC or 12 V DC (5V DC requires an external power supply)
320 mA/channel |
| Maximum Input Frequency |
400 kHz |
| Stegmann Option |
| Encoder Voltage Supply: |
11.5V DC @ 130 mA |
| Hi-Resolution Feedback: |
Sine/Cosine 1V P-P Offset 2.5 |
| Maximum Cable Length: |
182 m (600 ft.) |
| RS-485 Interface: |
Hi-Resolution Feedback Option card obtains the following information via the Hiperface RS-485 interface shortly after powerup:
Address, Command Number, Mode, Number of turns, Number of Sine/Cos cycles, Checksum |
Customer-I/O Plug (P1) -
Hi Res: |
Allen-Bradley PN: S94262912
Weidmuller PN: BL3.50/90/12BK |
|
| Resolver Option: |
| Excitation Frequency |
2400 Hz |
| Excitation Voltage |
4.25-26 Vrms |
| Operating Frequency Range |
1 - 10 kHz |
| Resolver Feedback Voltage |
2V ± 300 mV |
| Maximum Cable Length |
304.8 meters (1000 ft.) |
|