| Category |
Specification |
380/400V
Drive |
480V
Drive |
500V
Drive |
600V
Drive |
690V
Drive |
| Protection |
AC Input Overvoltage Trip: |
475VAC |
570VAC |
611VAC |
690VAC |
- |
| Bus Overvoltage Trip: |
675VDC |
810VDC |
810VDC |
1013VDC |
- |
| Bus Undervoltage Trip: |
Adjustable |
| Nominal Bus Voltage: |
540VDC |
648VDC |
645VDC |
810VDC |
- |
| Heat Sink Thermistor: |
Monitored by microprocessor overtemp trip |
Drive Overcurrent Trip |
| Software Current Limit: |
Calculated value, 105% of motor rated to 200% of drive rated.
105% of 3 sec. rating (158%-210%)
143% of 3 sec. rating (215%-287%) |
| Hardware Current Limit: |
105% of 3 sec. rating (158%-210%) |
|
| Line Transients: |
Up to 6000 volts peak per IEEE C62.41-1991 |
| Control Logic Noise Immunity: |
Showering arc transients up to 1500V peak |
| Power Ride-Thru: |
15 milliseconds at full load |
| Logic Control Ride-Thru |
0.25 sec., drive not running |
| Ground Fault Trip: |
Ground Fault Trip: |
| Short Circuit Trip: |
Phase-to-phase on drive output |
Agency
Certification |
The drive is also designed to meet the following specifications:
- NFPA 70 - US National Electrical Code
- NEMA ICS 3.1 - Safety standards for Construction and Guide for Selection, Installation and Operation of Adjustable Speed Drive Systems.
- IEC 146 - International Electrical Code.
|
 |
Listed to UL508C and CAN/CSA-C2.2 No. 14-M91. |
 |
Marked for all applicable European Directives
EMC Directive (89/336/EEC)
Emissions
EN 61800-3 Adjustable Speed electrical power drive systems
Part 3
Low Voltage Directive (73/23/EEC)
EN 50178 Electronic Equipment for use in Power Installations |
| Category |
Specification |
| Environment |
Altitude: |
1000 m (3300 ft.) max. without derating |
Surrounding Air Temperature without
Derating: |
Based on drive rating, refer to Drive Frame ahapters |
| Storage Temperature (all const.): |
-40 to 70° C (-40 to 158° F) |
| Relative Humidity: |
5 to 95% non-condensing |
| Shock: |
15G peak for 11 ms duration (+/- 1.0 ms) |
| Vibration: |
2 mm (0.0787 in.) displacement, 1G peak
EN50178 / EN60068-2-6 |
| Atmosphere: |
Important: Drive must not be installed in an area where the
ambient atmosphere contains volatile or corrosive gas, vapors
or dust. If the drive is not going to be installed for a period of
time, it must be stored in an area where it will not be exposed to
a corrosive atmosphere. |
| Electrical |
Voltage Tolerance: |
- 10% of minimum, + 10% of maximum. |
| Frequency Tolerance: |
47-63 Hz |
| Input Phases: |
Three-phase input provides full rating for all drives. Single-phase operation provides 50% of rated current. |
| Displacement Power Factor: |
0.98 across speed range |
| Efficiency: |
97.5% at rated amps, nominal line volts. |
Max. Short Circuit Current Rating:
Using Recommended Fuse or Circuit
Breaker Type |
Maximum short circuit current rating to match specified fuse/circuit breaker capability.
</= 200,000 Amps |
| Maximum Drive to Motor Power Ratio |
The drive to motor rating cannot exceed a 2:1 ratio |
| Control |
Method
Induction Motor:
Brushless Motor: |
Sine coded PWM with programmable carrier frequency, Indirect
Self-Organized, Field-Oriented Control, Current-regulated. Ratings apply to all drives (refer to the De-rating Guidelines in the
PowerFlex Reference Manual). The drive can be supplied as 6
pulse or 12 pulse in a configured package. |
Carrier Frequency
Frames 0 - 4 |
Drive rating: 2 kHz, Settings: 2, 4, 8, 10 kHz |
| Output Voltage Range: |
0 to rated motor voltage |
| Output Frequency Range: |
0 – 320 Hz |
Speed Regulation:
|
| Without Feedback |
0.1% of base speed across 120:1 speed range
120:1 operating range
50 rad/sec bandwidth |
| With Feedback |
0.001% of base speed across 120:1 speed range
1000:1 operating range
300 rad/sec bandwidth |
|
| Torque Regulation: |
| Without Feedback |
+/-10%, 600 rad/sec bandwidth |
| With Feedback |
+/-5%, 2500 rad/sec bandwidth |
|
| Selectable Motor Control: |
Field Oriented Control with and without a feedback device and Brushless motor control |
| Stop Modes: |
Multiple programmable stop modes including – Ramp, Coast and Current Limit |
| Accel/Decel |
Adjustable from 0.5 to 4.0 seconds |
| S-Curve Time |
110% Overload capability for up to 1 minute
150% Overload capability for up to 3 seconds |
| Current Limit Capability: |
Independent Motoring and Regenerative Power Limits programmable to 800% of rated output current |
| Electronic Motor Overload Protection |
Class 10 protection with speed sensitive response. Investigated by U.L. to comply with N.E.C. Article 430 U.L.
File E59272, volume 12. |
| Feedback |
Encoder Inputs |
Dual Channel Plus Marker, Isolated with differential transmitter Output (Line Drive) Incremental, Dual Channel Quadrature type |
| Encoder Voltage Supply |
5V DC or 12 V DC (5V DC requires an external power supply) |
| Maximum Encoder Input Frequency |
400khz |
| Stegmann Option |
| Encoder Voltage Supply |
11.5V DC @ 130 mA |
| Hi-Resolution Feedback |
Sine/Cosine 1V P-P Offset 2.5 |
| Maximum Cable Length |
182 m (600 ft.) |
| RS-485 Interface |
Hi-Resolution Feedback Option card obtains the following information via the Hiperface RS-485 interface shortly after powerup:
Address, Command Number, Mode, Number of turns, Number of Sine/Cos cycles, Checksum |
| Customer I/O Plus (P1) - HiRes |
Allen-Bradley PN: S94262912
Weidmuller PN: BL3.50/90/12BK |
|
| Resolver Option: |
| Excitation Freq |
2400 Hz |
| Excitation Voltage |
4.25 - 26 Vrms |
| Operating Frequency Range |
1 - 10 kHz |
| Resolver Feedback Voltage |
2V ± 300 mV |
| Maximum Cable Length |
304.8 meters (1000 ft.) |
|