753 Cat String

a
Code Type
20F PowerFlex 753
20G PowerFlex 755

b
Future Use

c
Input Type
Code Description Frames
1 6 Pulse, w/DC Terminals 2...5
4 DC Common Bus with Precharge 5...7
A 6 Pulse, w/o DC Terminals 6, 7

d
Enclosure
Code Description
F Flange Mount *‡
G IP54, NEMA/UL Type 12 §
N IP20/IP00, NEMA/UL Type Open†

* Frames 2...5 only and rated with a NEMA/UL Type 4x back
‡ Frames 6...7 require a user installed flange kit
§ Frames 2...5 only
† Frames 2...5 are IP20, Frames 6...7 are IP00

e
Voltage Rating
Code Voltage
C 400V AC
D 480V AC
f1
ND Rating
400V, 50Hz Input
Code Amps kW Frame
2P1 2.1 0.75 2
3P5 3.5 1.5 2
5P0 5.0 2.2 2
8P7 8.7 4 2
011 11.5 5.5 2
015 15.4 7.5 2
022 22 11 2
030 30 15 3
037 37 18.5 3
043 43 22 3
060 60 30 4
072 72 37 4 (5, G enc)
085 85 45 5
104 104 55 5 (6, G enc)
140 140 75 6
170 170 90 6
205 205 110 6
260 260 132 6 (7, G enc)
302 302 160 7
367 367 200 7
456 456 250 7

f2
ND Rating
480V, 60Hz Input
Code Amps HP Frame
2P1 2.1 1 2
3P4 3.4 2 2
5P0 5.0 3 2
8P0 8.0 5 2
011 11 7.5 2
014 14 10 2
022 22 15 2
027 27 20 3
034 34 15 3
040 40 30 3
052 52 40 4
065 65 50 4 (5, G enc)
077 77 60 5
096 96 75 5 (6, G enc)
125 125 100 6
156 156 125 6
186 186 150 6
248 248 200 6 (7, G enc)
302 302 250 7
361 361 300 7
415 415 350 7
g
Filtering and CM Cap configuration
Code Filtering Default CM Cap Configuration
A » Yes Jumper Removed
J » Yes Jumper Installed

 » In all cases, jumpers are included for field reconfiguration as desired.

H
Dynamic Braking
Code Internal Resistor
§
Internal Transistor
A No Yes
B Yes Yes
N No No

§ Frame 2 Only
‡ Standard on Frames 2...5, Optional on Frames 6...7 </div>