Drives Service & Support > Powerflex 753 > Specifications

Protection

AC Input Overvoltage Trip: 380/400V: 576V AC
480V: 576V AC
AC Input Undervoltage Trip: 380/400V: 250V AC
480V: 300V AC
Bus Overvoltage Trip: 380/400V: 815V DC
480V: 815V DC
Bus Undervoltage Shutoff/Fault: 380/400V: 200V DC
480V: 200V DC
Nominal Bus Voltage (Full Load): 380/400: 540V DC
480V: 648V DC
Drive Overcurrent Trip
  • Software Overcurrent Trip:
Calculated value, 105% of motor rated to 200% of drive rated
  • Hardware Overcurrent Trip:
105% of 3 sec. rating (158…210%)
  • Instantaneous Current Limit:
143% of 3 sec. rating (215…287%)
Line transients: up to 6000 volts peak per IEEE C62.41-1991
Control Logic Noise Immunity: Showering arc transients up to 1500V peak
Power Ride-Thru: 15 milliseconds at full load
Logic Control Ride-Thru: 0.5 seconds minimum, 2 seconds typical
Ground Fault Trip: Phase-to-ground on drive output
Short Circuit Trip: Phase-to-phase on drive output

 

Environment

Altitude: 1000 m (3300 ft) max. without derating
Maximum Surrounding Air
Temperature without De-rating:
Based on drive rating, See bottom of page.
Storage Temperature (all const.): –40 to 70° C (–40 to 158° F)
Atmosphere: Important: Drive must not be installed in an area where the ambient atmosphere contains volatile or corrosive gas, vapors or dust. If the drive is not going to be installed for a period of time, it must be stored in an area where it will not be exposed to a corrosive atmosphere.
Relative Humidity: 5 to 95% non-condensing
Shock:
Non-operational
Frame 2…6: 15 g peak for 11 ms duration (±1.0 ms)
Frame 7: 10 g peak for 11 ms duration (±1.0 ms)
Frame 2: 381 mm (15 in.) drop height
Frame 3…4: 330 mm (13 in.) drop height
Frame 5: 305 mm (12 in.) drop height
Frame 6…7: Meets International Safe Transit Association
(ISTA) test procedure 2B
Vibration (Operating): Frame 2: 1.000 mm (0.040 in.) displacement, 2 g peak
Frame 3…5: 1.000 mm (0.040 in.) displacement, 1.5 g peak
Frame 6…7: 1.000 mm (0.040 in.) displacement, 1 g peak
Sound
Frame Fan Speed Sound Level
2 50 CFM 63 db
3 80 CFM 64 db
4 160 CFM 72 db
5 260 CFM 77 db
6 252 CFM 73 db
7 252 CFM 74 db
Sound pressure measured at 2 meters

 

Electrical

DC Input Voltage Tolerance: ±10%
Frequency Tolerance: 47-63 Hz.
Input Phases: Three-phase input provides full rating for all drives.
Single-phase operation provides 50% of rated current.
Displacement Power Factor: 0.98 across entire speed range.
Efficiency: 97.5% at rated amps, nominal line volts.
DC Link Inductance ≥ 5%
Maximum Short Circuit Rating: 200,000 Amps symmetrical.
Actual Short Circuit Rating: Determined by AIC rating of installed fuse/circuit breaker.
Maximum Drive to Motor Power
Ratio
Recommended not greater than 2:1 ratio.

 

Control

Method: Sine coded PWM with programmable carrier frequency. Ratings apply to all drives (refer to the De-rating Guidelines in the PowerFlex Reference Manual). The drive can be supplied as 6 pulse.
Carrier Frequency: Default Drive Setting Frame 2: 4 kHz
Default Drive Setting Frame 7: 2 kHz
Frame 2 Settings: 2, 4, 6, 8, 10, 12 kHz
Frame 7 Settings: 2, 4, 8 KHz
Output Voltage Range: 0 to rated motor voltage
Output Frequency Range: 0…325 Hz @ 2 kHz carrier
0…650 Hz @ 4 kHz carrier
Frequency Accuracy
Digital Input:
Within ±0.01% of set output frequency.
Frequency Accuracy
Analog Input:
Within ±0.4% of maximum output frequency.
Frequency Control: Speed regulation - with Slip Compensation
0.5% of base speed across 40:1 speed range
40:1 operating range
Speed Control without feedback: 0.1% of base speed across 120:1 speed range
120:1 operating range
50 rad/sec bandwidth
Speed Control with feedback: 0.001% of base speed across 100:1 speed range
1000:1 operating range
190 rad/sec bandwidth
Torque Regulation without feedback: ±5%, 600 rad/sec bandwidth
Torque Regulation with feedback: ±5%, 2500 rad/sec bandwidth
Selectable Motor Control: Sensorless Vector with full tuning. Standard V/Hz with full custom capability.
Stop Modes: Multiple programmable stop modes including - Ramp, Coast, DC-Brake, Ramp-to-Hold and S-curve.
Accel/Decel: Two independently programmable accel and decel times. Each time may be programmed from 0 to 3600.10 seconds in 0.1 second increments.
S-Curve Time 0…100% of accel/decel time.
Intermittent Overload: 110% Overload capability for up to 1 minute
150% Overload capability for up to 3 seconds
Current Limit Capability: Proactive Current Limit programmable from 20 to 160% of rated output current. Programmable proportional gain.
Electronic Motor Overload
Protection:
Class 10 protection with speed sensitive response. Investigated by U.L. to comply with N.E.C. Article 430. U.L. File E59272, volume 12.

 

Standards

  • CE
    • EMC - EN61800-3
    • Low Voltage - EN61800-5-1
  • UL
  • cUL
  • C-Tick
  • TUV FS
  • SEMI F47
  • ROHS
  • EPRI
  • GOST-R

Enclosure & Ambient Operating Temperatures

Enclosure Ambient Frame
IP20, NEMA/UL Open Type 0…50 °C (32…122 °F) Frames 2…5, All Ratings
IP00, NEMA/UL Open Type 0…50 °C (32…122 °F) Frames 6 …7, All Ratings
IP20, NEMA/UL Type 1 (w/Hood) 0…40 °C (32…104 °F) Frames 2…5, All Ratings
IP20, NEMA/UL Type 1 (w/Label) 0…40 °C (32…104 °F) Frames 6 …7, All Ratings
Flange Mount – Front:
IP20, NEMA/UL Open Type
0…50 °C (32…122 °F) Frames 2…5, All Ratings
Flange Mount – Front:
IP00, NEMA/UL Open Type
0…50 °C (32…122 °F) Frames 6 …7, All Ratings
Back/Heat Sink:
IP66, NEMA/UL Type 4X
0…40 °C (32…104 °F) All Frames, All Ratings
Stand-alone/Wall Mount –
IP54, NEMA/UL Type 12
0…40 °C (32…104 °F) All Frames, All Ratings