| AC Input Overvoltage Trip: |
380/400V: 611V AC
480V: 611V AC |
| AC Input Undervoltage Trip: |
380/400V: 235V AC
480V: 235V AC |
| Bus Overvoltage Trip: |
380/400V: 815V DC
480V: 815V DC |
| Bus Undervoltage Shutoff/Fault: |
380/400V: 333V DC
480V: 333V DC |
| Nominal Bus Voltage (Full Load): |
380/400: 517V DC
480V: 621V DC |
| Drive Overcurrent Trip |
- Software Overcurrent Trip:
|
Calculated value, 105% of motor rated to 200% of drive rated |
- Hardware Overcurrent Trip:
|
105% of 3 sec. rating (158…210%) |
- Instantaneous Current Limit:
|
143% of 3 sec. rating (215…287%) |
| Line transients: |
up to 6000 volts peak per IEEE C62.41-1991 |
| Control Logic Noise Immunity: |
Showering arc transients up to 1500V peak |
| Power Ride-Thru: |
15 milliseconds at full load |
| Logic Control Ride-Thru: |
0.5 seconds minimum, 2 seconds typical |
| Ground Fault Trip: |
Phase-to-ground on drive output |
| Short Circuit Trip: |
Phase-to-phase on drive output |
| Altitude: |
1000 m (3300 ft) max. without derating |
Maximum Surrounding Air
Temperature without De-rating: |
Based on drive rating, See bottom of page. |
| Storage Temperature (all const.): |
–40 to 60° C (–40 to 140° F) |
| Atmosphere: |
Important: Drive must not be installed in an area where the
ambient atmosphere contains volatile or corrosive gas,
vapors or dust. If the drive is not going to be installed for a
period of time, it must be stored in an area where it will not be
exposed to a corrosive atmosphere. |
| Relative Humidity: |
5 to 95% non-condensing |
Shock:
Non-operational |
15G peak for 11ms duration (±1.0 ms) |
| Vibration: |
2 mm (0.0787 in.) displacement, 1G peak
EN50178 / EN60068-2-6 |
| AC Input Voltage Tolerance: |
±10% |
| Frequency Tolerance: |
47-63 Hz. |
| Input Phases: |
Three-phase input provides full rating for all drives.
Single-phase operation provides 50% of rated current. |
| Displacement Power Factor: |
0.98 across entire speed range. |
| Efficiency: |
97.5% at rated amps, nominal line volts. |
| Maximum Short Circuit Rating: |
200,000 Amps symmetrical. |
| Actual Short Circuit Rating: |
Determined by AIC rating of installed fuse/circuit breaker. |
Maximum Drive to Motor Power
Ratio |
Recommended not greater than 2:1 ratio. |
| Method: |
Sine coded PWM with programmable carrier frequency.
Ratings apply to all drives (refer to the De-rating Guidelines
in the PowerFlex Reference Manual). The drive can be
supplied as 6 pulse or 12 pulse in a configured package. |
| Carrier Frequency: |
Drive rating: 4 kHz
Settings: 2, 4, 6, 8, 10, 12 kHz |
| Output Voltage Range: |
0…650 Hz |
| Output Frequency Range: |
0…320 Hz |
Frequency Accuracy
Digital Input: |
Within ±0.01% of set output frequency. |
Frequency Accuracy
Analog Input: |
Within ±0.4% of maximum output frequency. |
| Frequency Control: |
Speed regulation - with Slip Compensation
0.5% of base speed across 40:1 speed range
40:1 operating range |
| Speed Control without feedback: |
0.1% of base speed across 120:1 speed range
120:1 operating range
50 rad/sec bandwidth |
| Speed Control with feedback: |
0.001% of base speed across 100:1 speed range
1000:1 operating range
190 rad/sec bandwidth |
| Torque Regulation without feedback: |
±5%, 600 rad/sec bandwidth |
| Torque Regulation with feedback: |
±5%, 2500 rad/sec bandwidth |
| Selectable Motor Control: |
Sensorless Vector with full tuning. Standard V/Hz with full custom capability. |
| Stop Modes: |
Multiple programmable stop modes including - Ramp, Coast, DC-Brake, Ramp-to-Hold and S-curve. |
| Accel/Decel: |
Two independently programmable accel and decel times. Each time may be programmed from 0 to 3600.10 seconds in 0.1 second increments. |
| S-Curve Time |
0…100% of accel/decel time. |
| Intermittent Overload: |
110% Overload capability for up to 1 minute
150% Overload capability for up to 2 seconds |
| Current Limit Capability: |
Proactive Current Limit programmable from 20 to 160% of rated output current. Programmable proportional gain. |
Electronic Motor Overload
Protection: |
Class 10 protection with speed sensitive response. Investigated by U.L. to comply with N.E.C. Article 430. U.L. File E59272, volume 12. |