Reliance Electric™ Drives Service & Support
DC2 Drives
Specifications
Controller Ratings
| Motor HP |
Input Voltage VAC |
Rated AC Line Amps ^ |
Input KVA |
DC Armature Voltage |
Rated Armature Current (Amps) |
Available Field Voltage |
Rated Field Current (Amps) |
| .25 |
115 |
3.1 |
.36 |
90 |
2.5 |
50 |
2.0 |
| .33 |
115 |
4.2 |
.48 |
90 |
3.7 |
50 |
2.0 |
| .50 |
115 |
6.2 |
.71 |
90 |
5.0 |
50 |
2.0 |
| .50 |
230 |
3.1 |
.71 |
180 |
2.5 |
100 |
2.0 |
| .75 |
115 |
9.4 |
1.0 |
90 |
7.5 |
50 |
2.0 |
| .75 |
230 |
4.7 |
1.0 |
180 |
3.7 |
100 |
2.0 |
| 1* |
115 |
12.5 |
1.4 |
90 |
10.0 |
50 |
2.0 |
| 1* |
230 |
6.2 |
1.4 |
180 |
5.0 |
100 |
2.0 |
| 1.5 |
230 |
9.4 |
2.2 |
180 |
7.5 |
100 |
2.0 |
| 2* |
230 |
12.5 |
2.9 |
180 |
10.0 |
100 |
2.0 |
^ Includes motor field current.
* DC2 Series 50 designs must be mounted to a metal plate 18" x 18" to meet 1 HP @ 115 VAC and 2 HP @ 230 VAC or an optional heat sink (HS1-50) can be purchased.
Service Conditions
| Elevation |
Up to 3300 feet (1000 meters) |
| Ambient Temperature |
Enclosed Models
|
32°F to 104°F / 0°C to 40°C |
Chassis Models
|
32°F to 131°F / 0°C to 55°C |
| AC Line Voltage Variation |
+/- 10% Rated Voltage |
| AC Frequency |
48 to 62 Hz |
| Atmosphere |
Non Condensing Relative |
| Humidity |
5 to 95 % |
Application Data
| Service Factor |
1.0 |
| Maximum Load |
150% for 1 Minute |
| Speed Regulation |
Voltage Feedback
|
2-5% (95% Load Change) |
Tachometer Feedback
|
1% (95% Load Change) |
| Speed Range |
20:1 with armature voltage feedback |
| Speed Range |
30:1 with tachometer feedback |
Feedback and reference potentiometer circuits are not isolated from main power. Isolation transformers are mandatory for tachometer feedback operation using a type RE020 20.8 VDC/1000 RPM tachometer (Model R20E8000). Consult instruction manual D2-3231 for other recommended or mandatory uses of isolation transformers and complete application information.
Adjustments
| Maximum Speed (% of rated) |
under 50 to 100% |
| Minimum Speed (% of rated) |
under 5 to 50% |
| Current Limit (% of rated) |
adjustable to 150% |
| Acceleration Rate |
0.3 to 40 Seconds Linear |
| Deceleration Rate |
0.3 to 40 Seconds Linear |
| IR Drop Compensation |
5 to 10% |
|