FlexPak 3000 Drives

Regulator LED Status Lights

Two LEDs on the Regulator board indicate the operating status of the Regulator board. The cover on the OIM must be removed to observe these LEDs. Check these LEDs when the OIM is not communicating with the regulator. Typically, there will be no fault indication on the display when the OIM is not communicating with the Regulator board. If a fault can be displayed, the fault would be OIM COMMUNICATIONS TIMEOUT (F00011).

The two LEDS are labeled CPU OK and OIM COMM OK. CPU OK will be on whenever the inputs and outputs are being scanned (I/O is not scanned during power- up diagnostics and following certain faults). OIM COMM OK will be on whenever the Regulator board and the OIM are communicating properly. The following table summarizes the possible states of the two LED indicators.

CPU
OK LED
OIM
COMM
OK LED
Indication and Action
Off Off
  • No power - verify that the drive power is on; check voltages at the Regulator board.
  • LED failure - cycle power and verify that both LEDs illuminate briefly (lamp test).
  • Power-up diagnostics failed - replace the Regulator board.
On
  • Combination not used.
Blink
  • Combination not used.
On Off
  • I/O is being scanned; the regulator is not communicating with the OIM - check OIM cable; check voltages at the OIM.
On
  • I/O is being scanned; the regulator is communicating with the OIM; no faults - this is the normal condition, no action is required.
  • I/O is being scanned; the regulator is communicating with the OIM; diagnose/correct the fault condition and reset the fault from the selected control source fault reset.
  • Power-up diagnostics in progress (lamp test).
Blink
  • Combination not used.
Blink Off
  • I/O is not being scanned; the Regulator board is not
    communicating with the OIM; check the OIM cable or cycle power.
On
  • I/O is not being scanned; the Regulator board is
    communicating with the OIM; record information on the fault, press the OIM fault reset key.
Blink
  • I/O is not being scanned, the Regulator board is not
    communicating with the OIM; record any information about the fault and cycle power.

 

Support Options
Discussion Forum
Paid Support Options
Obsolete Support Options

Electronic Data Sheets (EDS)

Nameplate Locator
Product Advisories
Firmware & Software Updates Web Updates
   
Get Literature
Knowledgebase
Drive Drawings
Technical Documents
NEMA Documents
Electronics Maintenance
   
Contact Us
Email a Technical Question
Who do I Call?
Meet the Support Team
   
Extra
Rockwell Modem Support
Environmental Commitment